Thermal conductivity, written λ (lambda), measures a material's ability to conduct heat. It is expressed in watts per metre-kelvin, W/(m·K), and corresponds to the heat flow crossing one metre of thickness of the material for a one-kelvin temperature difference. The lower λ, the more insulating the material: still air and foams have a very low λ, metals a very high one.
The SI unit is W/(m·K) (sometimes written W/m·°C, equivalent for a temperature difference). It describes an intrinsic property of the material, independent of its thickness: λ characterises the matter, not the wall. It is the building block of all building thermal calculations.
Physically, λ results from conduction in the solid matter and, for porous insulants, from conduction and radiation within the trapped air cavities. This is why the best insulants exploit still air (or gas) immobilised in a fine structure: static air conducts heat very poorly.
Conductivity links the thickness of a layer to its thermal resistance:
R = e / λ (R in m²·K/W, e in m, λ in W/(m·K))So, for a target thermal resistance, the lower λ, the less thickness is needed. This is the central relationship between the material (λ) and the performance of the layer (R), which is itself aggregated into the wall's U-value.
These indicative values, drawn from building-physics literature, place the main families of materials:
| Material | Indicative λ — W/(m·K) | Behaviour |
|---|---|---|
| Still air | ≈ 0.025 | Very insulating (if it does not circulate) |
| Insulants (wools, foams, wood fibre) | ≈ 0.030 – 0.045 | Dedicated insulants |
| Wood | ≈ 0.12 – 0.18 | Weakly conductive |
| Brick, plaster | ≈ 0.4 – 0.9 | Moderately conductive |
| Stone, concrete | ≈ 1.3 – 2.3 | Strongly conductive |
| Steel | ≈ 50 | Conductive (thermal bridge) |
Conductivity is measured in the laboratory, on a test specimen, using standardised methods:
The value depends on the mean test temperature, on density and above all on moisture: a damp material conducts heat far more. Data sheets therefore declare a λD value at standardised conditions.
This page complements the Thermal correction of facades guide.