The U-value, or surface thermal transmittance, measures the heat flow crossing one square metre of wall for a one-kelvin temperature difference between the two environments. It is expressed in watts per square metre-kelvin, W/(m²·K), and is calculated by U = 1/R_total. The lower U, the better the wall performs and the more it limits heat losses. It is the reference indicator for comparing walls.
The SI unit is W/(m²·K). The U-value characterises a complete wall as seen by the heat flow: unlike resistance R (which "slows" the flow), U expresses how much heat actually passes per unit area and per degree of difference. A high-performing wall lets little heat through: its U is low.
The U-value replaces the older k-value once used in some countries; it is the same physical notion, with a designation harmonised by the European standards.
The U-value is the inverse of the total thermal resistance of the wall:
U = 1 / R_total = 1 / (Rsi + ΣR + Rse) (U in W/(m²·K))where Rsi and Rse are the inside and outside surface resistances, and ΣR the sum of the layer resistances (each R = e/λ). This element-by-element calculation method is standardised by ISO 6946. Improving a wall's insulation means increasing R_total, hence lowering U.
For joinery, several coefficients are distinguished: Ug for the glazing alone, Uf for the frame, and Uw for the complete window, which combines glazing, frame and the thermal bridge of the spacer. Uw is the reference for comparing windows. The target U-values for walls and windows are set by the building regulations in force, which vary depending on local building regulations.
These markers illustrate the gap between an uninsulated wall and an insulated one; they are orders of magnitude, not project values:
| Wall (indicative example) | Indicative U — W/(m²·K) | Reading |
|---|---|---|
| Old uninsulated wall | ≈ 1.5 – 2.5 | High losses |
| Moderately insulated wall | ≈ 0.4 – 0.8 | Intermediate performance |
| Well insulated wall | ≈ 0.15 – 0.25 | Low losses |
| Single glazing | ≈ 5 – 6 | Very lossy |
| High-performance double glazing (Uw) | ≈ 1.1 – 1.4 | Good current level |
The practical value of the U-value is that it lets you quantify a wall's heat losses directly. The flow lost through an area A for a temperature difference ΔT between inside and outside is:
Φ = U · A · ΔT (Φ in W, A in m², ΔT in K)For example, for 10 m² of wall and a 20 K difference, moving from an indicative U of 2.0 to 0.25 W/(m²·K) cuts the flow from 400 W to 50 W in this simplified example: it is the same wall, better insulated, letting eight times less heat escape. Summed over all the walls, this calculation feeds a building's heat-loss balance.
U is most often calculated (a simulation from the layers and their λ values). On an existing building it can be measured in situ by the heat flow meter method described by the ISO 9869 standard: a heat flow meter and temperature probes record flow and differences over several days, and U is obtained by averaging over the measurement period.
It is important to distinguish:
To illustrate the ISO 6946 method, consider a fictitious wall made of surface resistances and two layers, with purely indicative values:
| Element | Indicative R — m²·K/W |
|---|---|
| Rsi (inside surface) | ≈ 0.13 |
| Masonry | ≈ 0.30 |
| Insulant | ≈ 2.86 |
| Rse (outside surface) | ≈ 0.04 |
| R_total | ≈ 3.33 |
First sum all the resistances (surface ones included), then invert the total. This example is an illustrative order of magnitude: the real values must come from the declared λ of the materials.
This page complements the Thermal correction of facades guide.