U-value: the thermal transmittance of a wall

What does the U-value measure?

The U-value, or surface thermal transmittance, measures the heat flow crossing one square metre of wall for a one-kelvin temperature difference between the two environments. It is expressed in watts per square metre-kelvin, W/(m²·K), and is calculated by U = 1/R_total. The lower U, the better the wall performs and the more it limits heat losses. It is the reference indicator for comparing walls.

Unit and physical meaning

The SI unit is W/(m²·K). The U-value characterises a complete wall as seen by the heat flow: unlike resistance R (which "slows" the flow), U expresses how much heat actually passes per unit area and per degree of difference. A high-performing wall lets little heat through: its U is low.

The U-value replaces the older k-value once used in some countries; it is the same physical notion, with a designation harmonised by the European standards.

Calculation formula

The U-value is the inverse of the total thermal resistance of the wall:

U = 1 / R_total = 1 / (Rsi + ΣR + Rse)  (U in W/(m²·K))

where Rsi and Rse are the inside and outside surface resistances, and ΣR the sum of the layer resistances (each R = e/λ). This element-by-element calculation method is standardised by ISO 6946. Improving a wall's insulation means increasing R_total, hence lowering U.

The case of windows (Uw)

For joinery, several coefficients are distinguished: Ug for the glazing alone, Uf for the frame, and Uw for the complete window, which combines glazing, frame and the thermal bridge of the spacer. Uw is the reference for comparing windows. The target U-values for walls and windows are set by the building regulations in force, which vary depending on local building regulations.

Indicative values (orders of magnitude)

These markers illustrate the gap between an uninsulated wall and an insulated one; they are orders of magnitude, not project values:

Wall (indicative example)Indicative U — W/(m²·K)Reading
Old uninsulated wall≈ 1.5 – 2.5High losses
Moderately insulated wall≈ 0.4 – 0.8Intermediate performance
Well insulated wall≈ 0.15 – 0.25Low losses
Single glazing≈ 5 – 6Very lossy
High-performance double glazing (Uw)≈ 1.1 – 1.4Good current level
Generic illustrative figures. Project values must come from standardised calculations (ISO 6946) or from product data sheets, never from estimates.

U and heat losses

The practical value of the U-value is that it lets you quantify a wall's heat losses directly. The flow lost through an area A for a temperature difference ΔT between inside and outside is:

Φ = U · A · ΔT  (Φ in W, A in m², ΔT in K)

For example, for 10 m² of wall and a 20 K difference, moving from an indicative U of 2.0 to 0.25 W/(m²·K) cuts the flow from 400 W to 50 W in this simplified example: it is the same wall, better insulated, letting eight times less heat escape. Summed over all the walls, this calculation feeds a building's heat-loss balance.

How is U measured?

U is most often calculated (a simulation from the layers and their λ values). On an existing building it can be measured in situ by the heat flow meter method described by the ISO 9869 standard: a heat flow meter and temperature probes record flow and differences over several days, and U is obtained by averaging over the measurement period.

It is important to distinguish:

  • Calculated U (simulation): derived from the declared characteristics of the materials, in an idealised regime.
  • Measured U (site): derived from real readings, which capture the actual state of the wall (moisture, defects, heterogeneities).

Example of a layer-by-layer calculation

To illustrate the ISO 6946 method, consider a fictitious wall made of surface resistances and two layers, with purely indicative values:

ElementIndicative R — m²·K/W
Rsi (inside surface)≈ 0.13
Masonry≈ 0.30
Insulant≈ 2.86
Rse (outside surface)≈ 0.04
R_total≈ 3.33
U = 1 / 3.33 ≈ 0.30 W/(m²·K)

First sum all the resistances (surface ones included), then invert the total. This example is an illustrative order of magnitude: the real values must come from the declared λ of the materials.

Limits of interpretation

  • U describes a steady state: it says nothing about summer comfort, inertia or time lag.
  • U does not account for radiative transfers or the cold-wall sensation, which belongs to surface temperature.
  • The U of a main wall does not include linear thermal bridges (coefficient ψ, ISO 10211) that add to the overall heat-loss calculation.
  • The real U depends on workmanship quality and moisture, which can degrade the stated performance.

Go further

This page complements the Thermal correction of facades guide.