A building's ground floor rests on its perimeter wall; at this junction, the floor insulation and the wall insulation struggle to meet, and the masonry provides a conductive path between the inside and the surrounding environment (ground, crawl space or basement). This thermal bridge at the base of the wall lowers the temperature at floor level, creates a sensation of a cold floor and a risk of condensation along the skirting boards. It is quantified by a linear coefficient ψ (W/m·K) and depends strongly on the position of the insulation and the type of substructure.
The physics of the bridge depends on what lies beneath the floor:
In all three cases, the sensitive point is the ground floor / perimeter wall junction, where floor insulation, wall and substructure meet.
The bridge is characterised by a linear coefficient ψ applied to the perimeter of the ground floor.
Heat loss at the base of the wall: Hψ = ψ · Pfloor (P = perimeter of the ground floor in m)The value is determined by the default values of EN ISO 14683 or by a detailed ISO 10211 calculation. For slabs on ground, calculating the heat loss through the ground also involves the standard ISO 13370, which deals with heat transfer to the ground and separates the surface part from the perimeter part.
| Junction configuration | Indicative ψ (W/m·K) | Cold floor felt |
|---|---|---|
| Floor and wall insulation in continuity (perimeter insulation) | ≈ 0.10 – 0.30 | Limited |
| Floor insulation only, base of wall untreated | ≈ 0.30 – 0.60 | Pronounced |
| No insulation at the base of the wall (crawl space) | ≈ 0.50 – 0.90 | Strong |
The ground-floor bridge results in a cold floor around the perimeter and in a low internal surface temperature along the walls, at floor level. Condensation is frequently observed behind low furniture and along skirting boards, with a risk of mould. It is also a source of discomfort from cold feet, even when the ambient air is at a good temperature.
The principle is to re-establish the continuity of the insulation between the floor and the wall. Depending on the access and the type of substructure:
As with any critical junction, this bridge is not "removed": it is strongly reduced through the continuity of the application, then the result is verified by calculation or by thermography. The wall-floor junction describes the general geometry of this junction.
This guide complements the Thermal correction of buildings dossier and the Thermal bridges cluster. Isoltech Green is a European distributor; the choice of a solution falls to a project study.