A thermal bridge is a localised area of a building envelope where heat flow is more intense than in the plain field, due to a break in the insulation or an unfavourable geometry. It is found mainly at junctions between elements: slab edges, balconies, window reveals, party walls, wall-floor and wall-roof junctions. Its effects are increased heat loss, a locally colder wall, a risk of surface condensation and of mould. It is quantified by a linear coefficient ψ (W/m·K) or a point coefficient χ (W/K).
Thermal bridges are classified by their geometry and their cause. This distinction guides both the calculation and the treatment.
These are the most common. They develop along a line: the junction between two elements (wall and floor, wall and roof, facade corner, window perimeter). They are quantified by the linear thermal transmittance ψ (psi), expressed in W/(m·K). The additional heat loss of the bridge is obtained by multiplying ψ by the length of the junction.
Localised at a point rather than along a line, these correspond, for example, to a fixing passing through the insulation or to the intersection of two linear junctions. They are quantified by the point coefficient χ (chi), in W/K. Their contribution is often smaller than that of linear bridges, but it can matter when they are repeated.
We also distinguish the geometric bridge, caused by the shape of the envelope (an outward corner exposes more external than internal surface, so the flow is concentrated), from the structural bridge, caused by a conductive element that interrupts the insulation (concrete slab, party wall, metal support). Finally, an integral bridge lies within a plain element (rails, framing, fixings), whereas a junction bridge lies at the junction between two elements. One single critical junction, such as a slab edge, often combines several of these characteristics.
Quantification relies on a standardised framework. The thermal resistance of plain elements is first calculated to ISO 6946; the junction coefficients ψ are then determined at two levels of precision:
Depending on local regulations, these coefficients feed into the regulatory energy calculation, where junction thermal bridges are accounted for in the envelope heat-loss balance.
Generic benchmarks drawn from published building physics, to situate the families of junctions. The real values depend on the composition and on the workmanship.
| Junction | Indicative ψ (W/m·K) | Sensitivity |
|---|---|---|
| Outward facade corner (geometric) | ≈ 0.05 – 0.15 | Moderate |
| Frame-to-masonry junction (window perimeter) | ≈ 0.05 – 0.30 | Depends on the fitting |
| Slab edge on facade (horizontal floor junction) | ≈ 0.10 – 0.80 | High |
| Cantilevered balcony (through slab) | ≈ 0.40 – 1.00 | Very high |
A thermal bridge combines three effects that reinforce one another:
The principle is to ensure the continuity of the insulation at critical junctions. External wall insulation (EWI) wraps the structure and restores this continuity; internal wall insulation (IWI), more economical, leaves residual bridges at floors and party walls. In new build, thermal break units (covered by a European Technical Assessment, ETA) treat certain junctions from the outset. The realistic objective is never to cancel everything out, but to strongly reduce the bridges and to verify the result by calculation or by thermography.
This guide complements the Thermal correction of buildings dossier and serves as a gateway to the Thermal bridges cluster.