Guide · thermal bridge

Thermal bridge: definition, types and consequences

What is a thermal bridge?

A thermal bridge is a localised area of a building envelope where heat flow is more intense than in the plain field, due to a break in the insulation or an unfavourable geometry. It is found mainly at junctions between elements: slab edges, balconies, window reveals, party walls, wall-floor and wall-roof junctions. Its effects are increased heat loss, a locally colder wall, a risk of surface condensation and of mould. It is quantified by a linear coefficient ψ (W/m·K) or a point coefficient χ (W/K).

The types of thermal bridge

Thermal bridges are classified by their geometry and their cause. This distinction guides both the calculation and the treatment.

Junction (linear) thermal bridges, ψ

These are the most common. They develop along a line: the junction between two elements (wall and floor, wall and roof, facade corner, window perimeter). They are quantified by the linear thermal transmittance ψ (psi), expressed in W/(m·K). The additional heat loss of the bridge is obtained by multiplying ψ by the length of the junction.

Point thermal bridges, χ

Localised at a point rather than along a line, these correspond, for example, to a fixing passing through the insulation or to the intersection of two linear junctions. They are quantified by the point coefficient χ (chi), in W/K. Their contribution is often smaller than that of linear bridges, but it can matter when they are repeated.

Geometric or structural; integral or junction

We also distinguish the geometric bridge, caused by the shape of the envelope (an outward corner exposes more external than internal surface, so the flow is concentrated), from the structural bridge, caused by a conductive element that interrupts the insulation (concrete slab, party wall, metal support). Finally, an integral bridge lies within a plain element (rails, framing, fixings), whereas a junction bridge lies at the junction between two elements. One single critical junction, such as a slab edge, often combines several of these characteristics.

How is a thermal bridge quantified?

Quantification relies on a standardised framework. The thermal resistance of plain elements is first calculated to ISO 6946; the junction coefficients ψ are then determined at two levels of precision:

  • Default values (EN ISO 14683): the standard provides tabulated ψ values per type of junction, useful for a quick or regulatory estimate, but deliberately conservative and approximate.
  • Detailed calculation (ISO 10211): a numerical model of the detail (2D or 3D) gives a ψ or a χ specific to the real configuration, markedly more accurate than the default value.
Heat loss of a linear bridge:  Hψ = ψ · L  (ψ in W/(m·K), L junction length in m)

Depending on local regulations, these coefficients feed into the regulatory energy calculation, where junction thermal bridges are accounted for in the envelope heat-loss balance.

Orders of magnitude of ψ by type of junction

Generic benchmarks drawn from published building physics, to situate the families of junctions. The real values depend on the composition and on the workmanship.

JunctionIndicative ψ (W/m·K)Sensitivity
Outward facade corner (geometric)≈ 0.05 – 0.15Moderate
Frame-to-masonry junction (window perimeter)≈ 0.05 – 0.30Depends on the fitting
Slab edge on facade (horizontal floor junction)≈ 0.10 – 0.80High
Cantilevered balcony (through slab)≈ 0.40 – 1.00Very high
Generic orders of magnitude. The ψ of a given junction must be determined by the default values of EN ISO 14683 or, better, by a detailed ISO 10211 calculation on the real configuration. These benchmarks do not replace a project calculation.

What are the consequences?

A thermal bridge combines three effects that reinforce one another:

  • Increased heat loss: the concentrated flow increases heat losses; on an otherwise well-insulated envelope, junction bridges can represent a significant share of the balance.
  • Localised cold wall: the internal surface temperature drops at the bridge, creating a sensation of discomfort and a point where cold air drafts form.
  • Condensation and mould: at the coldest point, the indoor air can reach its dew point. The risk is assessed by the temperature factor fRsi, defined in EN ISO 13788: the colder the surface, the lower fRsi and the higher the risk of surface condensation and then of mould.

How is a thermal bridge treated?

The principle is to ensure the continuity of the insulation at critical junctions. External wall insulation (EWI) wraps the structure and restores this continuity; internal wall insulation (IWI), more economical, leaves residual bridges at floors and party walls. In new build, thermal break units (covered by a European Technical Assessment, ETA) treat certain junctions from the outset. The realistic objective is never to cancel everything out, but to strongly reduce the bridges and to verify the result by calculation or by thermography.

Limits of interpretation

  • The default values of EN ISO 14683 are conservative and do not replace a detailed ISO 10211 calculation for a specific project.
  • A ψ only has meaning when associated with a length-measurement convention (internal, external): two values can describe the same physical reality.
  • The reduction of a thermal bridge is established by standardised calculation or in-situ measurement, to be distinguished from a simple visual judgement.
  • Depending on the building, a conventional EWI or IWI may remain the best-suited solution: the choice depends on the structure, the heritage value and the project constraints.

This guide complements the Thermal correction of buildings dossier and serves as a gateway to the Thermal bridges cluster.