Thermal radiation is an exchange of energy as infrared radiation between surfaces, with no contact or intermediate air. Every surface emits and receives this radiation according to its temperature and emissivity. It is one of the three modes of heat transfer, together with conduction and convection. It explains why we feel cold near a cold wall even when the room air is warm.
Heat is transmitted in three ways: conduction (within the matter, linked to conductivity), convection (through the movement of air or a fluid) and radiation. The particularity of radiation is that it needs no material support: it crosses a vacuum and travels in a straight line from one surface to another, in the infrared for the usual building temperatures.
In a room, these three modes act simultaneously. The air heated by an emitter rises by convection, the walls conduct heat to the outside, and all the surfaces constantly exchange energy by radiation according to their temperature. Perceived comfort therefore depends as much on the temperature of the surfaces as on that of the air: this is why radiation deserves attention in its own right, distinct from the simple ambient temperature read on a thermometer.
The power radiated by a surface rises very quickly with its absolute temperature, according to the Stefan-Boltzmann law:
M = ε · σ · T⁴ (M in W/m², ε emissivity 0–1, σ ≈ 5.67 × 10⁻⁸ W/(m²·K⁴), T in kelvin)σ is the Stefan-Boltzmann constant. The power depends on the fourth power of the temperature in kelvin: a small surface-temperature difference clearly changes the radiated flow. The net exchange between two surfaces depends on the difference of their T⁴ and on their respective emissivities.
Emissivity ε, between 0 and 1, describes a surface's ability to emit (and absorb) infrared radiation relative to an ideal black body (ε = 1):
| Type of surface | Indicative emissivity ε | Behaviour |
|---|---|---|
| Renders, plaster, matt paint, wood | ≈ 0.90 – 0.95 | High emission (common building surfaces) |
| Glass, water | ≈ 0.90 – 0.95 | High emission in the infrared |
| Oxidised metal | ≈ 0.2 – 0.7 | Variable emission |
| Polished metal (aluminium, steel) | ≈ 0.05 – 0.10 | Low emission (reflective surface) |
The human body, at about 37 °C on the skin surface, radiates towards the colder surfaces around it. Facing a cold wall (a poorly insulated wall, a large glazed bay in winter), the body loses heat by radiation and we feel cold even if the room air is warm. It is a common form of radiant discomfort near cold walls.
To account for it, we use the mean radiant temperature (MRT): the view-angle-weighted average of the temperatures of the surfaces surrounding the occupant. The sensation of comfort depends on both the air temperature and this radiant temperature: this is what the operative temperature combines.
This mechanism sheds light on the value of treating the envelope: by raising the temperature of the inside surfaces of cold walls, you reduce the body's radiative losses towards those surfaces and improve comfort at equal air temperature. Conversely, a well-insulated wall whose inside face stays cold (a local defect, a thermal bridge) creates a localised point of radiant discomfort. This also explains the gentle warmth of radiant heating systems, which act directly on the mean radiant temperature rather than on the air temperature.
The infrared radiation emitted by surfaces is visualised with an infrared thermal camera (thermography) or a point surface temperature is measured with an infrared pyrometer. These instruments deduce the temperature from the flow received: the emissivity of the targeted surface must therefore be set correctly, or significant error follows, in particular on reflective metal surfaces.
Building thermography is carried out under controlled conditions (an indoor/outdoor temperature difference, no direct sunlight, the framework described by the EN 13187 standard for the qualitative detection of thermal irregularities in the envelope). The thermal image, which is qualitative (it locates anomalies), must be distinguished from a figured performance measurement.
This page complements the Thermal correction of facades guide.