The slab edge is the edge of the intermediate floor that terminates in the plane of the facade. Because the floor is concrete, a conductive material, it creates a horizontal junction thermal bridge over the whole length of the facade, at every storey. The indoor heat uses the slab to reach the outside, bypassing the insulation if it is installed on the inside. It is one of the most common and most extensive thermal bridges in a concrete-frame building. It is quantified by a linear coefficient ψ (W/m·K), often high, and it results in heat loss and a risk of condensation at the base of the wall.
In a typical concrete-frame construction, the floors rest on the facade walls and are flush with the external face. If the insulation is installed on the inside, it is interrupted at every floor: the slab directly links the heated indoor air to the cold facade. The bridge repeats at every storey and over the whole length of each facade, which makes it a major contributor to the heat-loss balance. It is both a structural bridge (a through concrete element) and a junction bridge (the wall-floor junction seen from the facade).
The heat loss is calculated by the linear coefficient ψ multiplied by the total length of the slab edges (facade length × number of storeys concerned).
Heat loss of the slab edges: Hψ = ψ · Lfacade · nstoreys (ψ in W/(m·K))The ψ is determined by the default values of EN ISO 14683 or by a detailed ISO 10211 calculation on the vertical cross-section. The benchmarks below show the considerable gap between an untreated slab and a junction wrapped from the outside.
| Configuration | Indicative ψ (W/m·K) | Weight in the balance |
|---|---|---|
| Internal insulation, untreated slab | ≈ 0.50 – 0.90 | Very high |
| Thermal break (new build, under ETA) | ≈ 0.10 – 0.30 | Reduced |
| External insulation wrapping the slab | ≈ 0.05 – 0.15 | Low |
The slab edge lowers the internal surface temperature along the floor-wall junction, often at the base of the wall of the upper storey and at the ceiling of the lower storey. Horizontal traces of condensation and dust ("thermal marbling") appear there, and sometimes mould. On an otherwise well-insulated envelope, the share of heat loss from the slab edges becomes proportionally significant, which justifies treating them as a priority during a renovation.
In renovation, the most effective route is external wall insulation: it wraps the slab and restores the continuity of the insulation over the full height of the facade, slab edge included. In new build, thermal break units (insulating elements integrated into the junction, under a European Technical Assessment, ETA) reduce the bridge from the outset. Internal wall insulation, less costly, on the contrary leaves a pronounced residual bridge at every slab.
A continuously applied facade render supports this logic of continuity, the slab being covered without panel joints. No treatment "removes" this bridge entirely: the objective is to strongly reduce it and then verify the result by calculation or by thermography. The wall-floor junction guide details the corresponding cross-section.
This guide is part of the Thermal correction of buildings dossier and the Thermal bridges cluster. Isoltech Green is a European distributor; the choice of a solution falls to a project study.