The junction between the facade wall and the roof brings together two distinct insulation layers — that of the walls and that of the covering — which struggle to meet. On a flat roof, the parapet (the masonry upstand around the perimeter) extends the wall above the roof and forms a fin exposed to the cold on three faces. These junctions create a linear thermal bridge at the top of the building, with heat loss and a cold point at the ceiling corner, where condensation and mould appear first. It is quantified by a linear coefficient ψ (W/m·K), which depends on the continuity between the wall insulation and the roof insulation.
Two families of configurations concentrate the thermal bridge at the top of the building:
The bridge is characterised by a linear coefficient ψ applied to the length of the wall-roof or parapet junction.
Heat loss of the top junction: Hψ = ψ · Ljunction (ψ in W/(m·K))The value is determined by the default values of EN ISO 14683 or, better, by a detailed ISO 10211 calculation, recommended for the parapet, whose geometry departs from the tabulated cases. The risk of condensation at the ceiling corner is assessed by the temperature factor fRsi (EN ISO 13788).
| Configuration | Indicative ψ (W/m·K) | Sensitivity |
|---|---|---|
| Wall/roof insulation continuity ensured | ≈ 0.05 – 0.20 | Low |
| Parapet insulated on its faces | ≈ 0.20 – 0.50 | Moderate |
| Untreated parapet (bare concrete upstand) | ≈ 0.50 – 0.90 | High |
The top-junction bridge lowers the internal surface temperature at the ceiling-wall connection, often visible as dark traces around the perimeter of the ceiling of the top storey. It increases roof heat loss, already a major item in the thermal balance since heat rises. Untreated, the parapet can also encourage waterproofing defects linked to temperature differences.
The principle remains the continuity of the insulation between the facade and the roof:
An external wall insulation that rises up to the parapet, a continuously applied render, makes this overlap easier. Here too, the bridge is not "removed": it is reduced and the result is verified by calculation or by thermography. The thermal treatment must always be coordinated with the roof waterproofing.
This guide complements the Thermal correction of buildings dossier and the Thermal bridges cluster. Isoltech Green is a European distributor; the choice of a solution falls to a project study.