Window thermal bridge

Why does a window create a thermal bridge?

A window creates a thermal bridge because its junction with the masonry interrupts the continuity of the insulation all around the opening: sill, lintel and reveals. The frame, the structural work and the insulation meet along a line where heat flow concentrates, all the more so if the window is set within the thickness of the wall rather than in the plane of the insulation. This junction is quantified by a linear coefficient ψ (W/m·K) that adds to the performance of the window and of the wall. Its effects are increased heat loss and a risk of condensation around the internal perimeter.

Where is a window's thermal bridge located?

The thermal bridge is not in the glazing nor in the plain wall: it develops along the four sides of the opening, at the junction between the window and the structural work. We distinguish four segments, each with its own geometry:

  • The sill (bottom rail): often the coldest point, because the concrete or stone sill extends the masonry outwards and conducts heat away.
  • The lintel (top rail): the load-bearing element above the opening, frequently in concrete, interrupts the insulation.
  • The reveals (side jambs): the vertical returns of the opening, dealt with in detail in the window reveals guide.

The sum of these four segments forms the junction thermal bridge of the opening. It is a junction, linear bridge: it is counted per metre of perimeter, not per unit area.

How is it quantified?

The overall performance of an installed window is not summed up by the window's Uw coefficient. The heat loss of the frame-to-masonry junction must be added, characterised by a linear coefficient ψ (psi) expressed in W/(m·K). Its heat loss is obtained by multiplying ψ by the length of the junction.

Heat loss of the opening junction:  Hψ = ψ · Lopening  (L = perimeter of the opening in m)

The ψ value is determined either by the default values of EN ISO 14683, tabulated per type of junction and deliberately conservative, or by a detailed calculation to ISO 10211, which models the real cross-section and gives a result specific to the configuration. The resistance of plain elements is calculated beforehand to ISO 6946. Depending on local regulations, these coefficients feed into the regulatory energy calculation.

Fitting configurationIndicative ψ (W/m·K)Effect
Frame in the plane of the insulation, with insulation return≈ 0.00 – 0.05Controlled junction
Set within the reveal with partial return≈ 0.05 – 0.15Moderate
Frame within the wall thickness, no return≈ 0.15 – 0.35Pronounced bridge
Generic orders of magnitude drawn from published building physics. The ψ of a real opening must be established by the default values of EN ISO 14683 or, better, by an ISO 10211 calculation on the project cross-section. These benchmarks do not replace a calculation.

Consequences: condensation and cold wall

The window perimeter is a point of health vigilance. At a cold frame, the internal surface temperature can fall below the dew point of the ambient air: condensation then appears on the reveal or the internal sill, followed, where humidity persists, by mould. The risk is assessed by the temperature factor fRsi defined in EN ISO 13788: the colder the surface, the lower fRsi and the higher the risk. A high-performance glazing on a poorly insulated frame sometimes shifts the cold point towards the perimeter, where condensation becomes visible.

How to reduce a window's thermal bridge?

The principle is to ensure the continuity of the insulation around the opening. Several levers combine:

  • Position the window in the plane of the insulation: with external insulation, setting the frame in the insulation plane strongly reduces the junction.
  • Ensure the insulation return on the reveals, sill and lintel, so that the insulation partly covers the frame.
  • Pay attention to air and water tightness of the sealing, distinct from insulation but complementary to prevent cold-air ingress.

External wall insulation (EWI) makes this treatment easier by wrapping the facade and allowing the return onto the reveals; internal wall insulation (IWI) leaves junctions that are harder to treat around the perimeter. It is never accurate to claim this bridge is "removed": the objective is to strongly reduce it through the continuity of the application, then to verify the result by calculation or by thermography.

Limits of interpretation

  • The ψ of an opening junction only has meaning with the length convention adopted (internal or external): two values can describe the same reality.
  • The default values of EN ISO 14683 are conservative and do not replace an ISO 10211 calculation on the real cross-section.
  • The performance of an installed window depends as much on the fitting detail as on the product: an excellent Uw does not cancel out a poorly treated junction.
  • Depending on the building (retained window, heritage constraint, available thickness), a conventional EWI or IWI may remain the best-suited solution.