Guide · critical junction

Window reveals

Why are window reveals thermal bridges?

Reveals — the vertical returns of masonry on the sides of an opening — are thermal bridges because the insulation is interrupted there to let the window frame through. The reveal masonry then remains bare or barely covered, and forms a cold strip on either side of the opening. The extent of the bridge depends above all on the insulation return: the more the insulation covers the reveal and reaches the frame, the smaller the junction. Without a return, the reveal becomes a cold point where condensation appears at the internal corner, with a risk of mould.

Reveal, jamb: what are we talking about?

The reveal is the side surface of an opening, between the facade plane and the window frame; the jamb refers to the whole return. Where the window guide deals with the entire perimeter (sill, lintel, reveals), this guide focuses on the side jambs, often the most delicate to treat, because the insulation must return there without reducing the glazed area excessively or hindering the opening.

What happens at the corner

The reveal combines two effects. First a geometric effect: the inward corner of the opening concentrates the flow lines, like any corner of the envelope. Then a structural effect: the uncovered masonry offers a direct conductive path between inside and outside. The combination lowers the internal surface temperature of the return, particularly in the corner where the reveal meets the plane of the wall. It is this internal corner that blackens first when a dwelling shows condensation around the windows.

How is it quantified?

The reveal bridge enters into the linear coefficient ψ (W/m·K) of the frame-to-masonry junction, counted over the length of the jambs. Its heat loss adds to those of the window and of the plain wall.

Contribution of the jambs:  Hψ = ψreveal · Ljambs  (L = combined height of the two jambs)

The value is determined by the default values of EN ISO 14683 or by a detailed ISO 10211 calculation on the horizontal cross-section of the opening. The temperature factor fRsi (EN ISO 13788) is what allows the risk of condensation at the reveal corner to be assessed: it is often the governing criterion, even before heat loss.

Insulation return on the revealIndicative ψ (W/m·K)Condensation risk
Continuous return up to the frame≈ 0.00 – 0.05Low
Partial return≈ 0.05 – 0.15Moderate
No return, bare masonry≈ 0.15 – 0.30High at the corner
Generic benchmarks drawn from published building physics. The real ψ depends on the thickness of the returning insulation, the position of the frame and the masonry; it is calculated to EN ISO 14683 or ISO 10211. These values do not replace a project calculation.

How to treat the thermal bridge of the reveals?

The key is the insulation return. With external wall insulation, the facade insulation is continued onto the reveal up to the frame: continuity is restored and the cold point largely disappears. When the available thickness is limited (narrow opening, sash flush with the reveal), higher-performance insulation on a small thickness is used, or the window is repositioned. With internal wall insulation, the return is made on the inside, but remains more constrained and often leaves a residual bridge.

A continuously applied facade render makes this return onto the reveals easier, with no panel joints to treat. It is still never accurate to say the bridge is "removed": it is strongly reduced through the continuity of the application, then verified by calculation or by in-situ thermography that the internal corner is no longer the critical cold point.

Limits of interpretation

  • Treating the reveal is inseparable from treating the sill and lintel: treating only one side shifts the cold point without solving it.
  • The default values of EN ISO 14683 are conservative; an ISO 10211 calculation on the real cross-section is more reliable.
  • The condensation criterion (fRsi) often takes priority over the heat-loss gain alone: a reveal may be acceptable energetically yet remain a health risk.
  • Depending on the opening and the available thickness, a conventional EWI or IWI may remain the best-suited solution.

This guide complements the Thermal correction of buildings dossier and the Thermal bridges cluster. Isoltech Green is a European distributor; the choice of a strategy falls to a project study.